Rhino ED RS232

Expansion module. Reads data from devices that support protocols such as IEC62056-21. Data transfer wireless via RF to the Rhino AP. Maximum transmission rate is 115200 b/s. Powered by external 5-12VDC power supply.

Device overview

  1. Power socket
  2. RS232 connection
  3. SMA ISM antenna connector
Rhino ED RS232

Technical parameters

Rhino communication Frequency range: 433MHz, ISM 2 channel
Power supply 5-12VDC (0.5A)
Supported communication protocol IEC62056-21
Configuration Over the Air (OTA)
Operating temperature range 0˚C – 85˚C (depending upon installed environment)
IP Class IP40 (not suitable for outdoor use)
Dimensions 52.5 mm x 90 mm x 65 mm (3 DIN modules)
Weight ~0.1 kg
Additional equipment 1 x ISM antenna with 3m cable and magnetic base
Required cable types Signals thickness – 0.129-1.31 MM² – 26-16AWG
Power supply thickens – 0.205-3.31 MM² – 24-12AWG

Connection diagram example

Data Sheet download
Rhino ED RS232 Schema